1) Yuanda company OEM manufacture special producing all kinds of electrical products have more then 25years.
2) our AC Contactor also approved "UL" "ETL" certificate.

Control Coil Voltage(DC Coil Operation)

LC1D series AC contactors are suitable for frequency 50/60Hz,rated insulation voltage up to 1000V,rated operation current 9~150A .It is mainly used for making and breaking electric circuits at a long distance & for frequent starting,stopping & controlling AC Motors.It is used in combination with thermal relay to compose a magnetic motor starter. The products comply with IEC60947-4.





2) our AC Contactor also approved "UL" "ETL" certificate.
1. General
1) Application: remote making & breaking circuits; protect circuit
from over-load when assembling with thermal over-load relay;..
frequent start-up and control of AC contactor;
2) Electric ratings: AC50/60Hz, 690V, up to 95A;
3) Utilization category: AC-3, AC-4;
4) Altitude: ≤2000m;
5) Ambient temperature: -5ºC~+40ºC;
6) Mounting category: III;
7) Mounting conditions: inclination between the mounting plane and the vertical plane should not exceed ±5°;.
8) Standard: IEC/EN 60947-4-1. .IEC/EN 60947-5-1. 9) Control Coil Voltage(AC Coil Operation)

Control Coil Voltage(DC Coil Operation)

Product Description
1.GeneralLC1D series AC contactors are suitable for frequency 50/60Hz,rated insulation voltage up to 1000V,rated operation current 9~150A .It is mainly used for making and breaking electric circuits at a long distance & for frequent starting,stopping & controlling AC Motors.It is used in combination with thermal relay to compose a magnetic motor starter. The products comply with IEC60947-4.
2.Specifications | ||||||||
Type | Thermal Rated Current (A) | Rated Current AC-3 380V(A) | Control Power AC-3(KW) | Rated Insulation | ||||
220V | 380V | 415V | 660V | Voltage(V) | Aux.Contact | |||
LC1-D09 | 20 | 9 | 2.2 | 4 | 4 | 5.5 | 660 | 3P+1NO+1NC |
LC1-D12 | 20 | 12 | 3 | 5.5 | 5.5 | 7.5 | ||
LC1-D18 | 32 | 18 | 4 | 7.5 | 9 | 9 | ||
LC1-D25 | 40 | 25 | 5.5 | 11 | 11 | 15 | ||
LC1-D32 | 50 | 32 | 7.5 | 15 | 15 | 18.5 | ||
LC1-D40 | 60 | 40 | 11 | 18.5 | 22 | 30 | ||
LC1-D50 | 80 | 50 | 15 | 22 | 25 | 33 | ||
LC1-D65 | 80 | 65 | 18.5 | 30 | 37 | 37 | ||
LC1-D80 | 125 | 80 | 22 | 37 | 45 | 45 | ||
LC1-D95 | 125 | 95 | 25 | 45 | 45 | 45 | ||
LC1-D115 | 200 | 115 | 30 | 55 | 59 | 80 | ||
LC1-D150 | 250 | 150 | 40 | 75 | 80 | 100 |